STRAIGHT PIPE
Page 132
MEASURING COMPLETED
INSULATION METHOD A
Applicable where contractor has
quoted unit rate per linear metre
of straight pipe and per each for
pipefitting.
STRAIGHT PIPE
Shall be measured from origin to
terminus point or junction, along
the
centerline of pipe. Measurements
shall be through valves, flanges
and fittings, but only if the
valves, flanges and fittings are
insulated. Elbows or bends shall
be measured through to the
intersection of the centre lines of
the pipe. Reducers shall be
counted as one fitting of the
larger size involved, and
omitted from the count of the
smaller size. Tees shall be
counted as one fitting, and if an
unequal tee, shall be counted as a
fitting of the smaller size.
Quantities shall be to the nearest
whole number (0.51 and larger to
the whole
number above).
FITTINGS - VALVES
Shall be counted per each.
(Flanges on flanged valves shall
be counted
separately).
FLANGES
Shall be counted per pair of
flanges. (Including flanges on
valves and
connections to vessels and
equipment).