MEASURING COMPLETED INSULATION METHOD A
Page 130
MEASURING COMPLETED
INSULATION METHOD A
Applicable where contractor has
quoted unit rate per linear metre
of straight pipe and per each for
pipefitting.
STRAIGHT PIPE
Shall be measured from origin to
terminus point or junction, along
the centerline of pipe.
Measurements shall be through
valves, flanges and fittings, but
only if the valves, flanges and
fittings are insulated. Elbows or
bends shall be measured through
to the intersection of the centre
lines of the pipe. Reducers shall
be counted as one fitting of the
larger size involved, and omitted
from the count of the smaller size.
Tees shall be counted as one
fitting, and if an unequal tee, shall
be counted as a fitting of the
smaller size. Quantities shall be
to the nearest whole number (0.51
and larger to the whole number
above).
FITTINGS-VALVES
Shall be counted per each.
(Flanges on flanged valves shall
be counted separately).
FLANGES
Shall be counted per pair of
flanges. (Including flanges on
valves and connections to
vessels and equipment).